RO 5000 LPH TECHNICAL SPECIFICATIONS
Flow Rate :
Feed Water : 9000 Liter Per Hour
Treated Water : 6000 Liter Per Hour
Reject Water : 3000 Liter Per Hour
1 | RAW WATER PUMP | ||
Purpose | To feed the Dual Media Filter at pressure more than 2.0 bar, which is min. operating pressure for filter. | ||
Specifications | a) MOC : CI | ||
b) Type : Horizontal Centrifugal | |||
c) Flow Rate : 14400 liters per hour | |||
d) Head : 25 m | |||
e) Power Required: 3 HP | |||
f) Electrical : 440 V, Three phase , 50 hz | |||
g) Cycle : 2900 rpm | |||
h) Make : Kirlosker, CRI, Crompton Greaves. | |||
i) Quantity : 1 No. | |||
2 | DUAL MEDIA FILTER | ||
Purpose | To remove the total suspended solids, dirt , iron and reduce silt density index which can foul the membranes | ||
Specifications | Vessel : | ||
a) Make : Pentier Or Equivalent b) Material of Construction : FRP c) Diameter : 30” | |||
d) Height : 72” mm | |||
e) Testing Pressure : 10 kg/cm2 | |||
f) Opening : Top and Bottom | |||
g) Quantity : 1 No. | |||
Valve : | |||
a) Make : Initiative | |||
b) Material of Construction : | |||
c) Type : Multiport Single lever value | |||
d) Size : 1.5” inches | |||
e) Maximum Flow Rate: 24000 LPH | |||
f) Working Pressure : 2-4 Bar | |||
g) Working : Down-Flow | |||
Media : | |||
Mixed bed sand media consisting of the following | |||
i) Gravel ii) Pebbles iii) Quartz Sand iv) Anthracite | |||
Average Porosity 50 micron particulate size | |||
Bed depth : 600 mm | |||
Pipelines & Accessories: | |||
Pipe of PVC 10 Bar tested pressure | |||
3 | ACTIVATED CARBON FILTER | ||
Purpose | To remove the total color, smell, odor, from the water. | ||
Specifications | Vessel: | ||
a) Make: Penteir Or Equilent b) Material of Construction: FRP c) Diameter: 30” | |||
d) Height: 72” mm | |||
e) Testing Pressure: 10 kg/cm2 | |||
f) Opening: Top & Bottom | |||
g) Quantity: 1 No. | |||
Valve: | |||
a) Make: Initiative | |||
b) Material of Construction: Noryl | |||
c) Type: Multiport Single lever value | |||
d) Size: 1.5 inches | |||
e) Maximum Flow Rate: 24000 LPH | |||
f) Working Pressure: 2-4 Bar | |||
g) Working: Down-Flow | |||
Media: | |||
Mixed bed sand media consisting of the following | |||
i) Gravel ii) Pebbles iii) Carbon | |||
Average Porosity 50 micron particulate size | |||
Bed depth: 600 mm | |||
Pipelines & Accessories: | |||
Pipe of PVC 10 Bar tested pressure | |||
4 | DOSING SYSTEM | ||
Purpose | To dose Antiscalant chemical to protect the scaling formation on RO membranes. | ||
Specifications | a) MOC : PP ( E-dose) | ||
b) Capacity : 6 LPH | |||
c) Pressure : 7 Bar | |||
d) Qty. : 1 No. | |||
5 | MICRON FILTER | ||
Purpose | To remove the fine particles up to 05 microns and reduce silt density index levels to acceptable level. | ||
Specifications | Cartridge Filter & Housing | ||
Housing : | |||
a) Make: Flowtec | |||
b) MOC of Housing: PP | |||
c) Length : 20” | |||
d) Diameter: 5.5” | |||
e) Quantity : 4 no. | |||
Cartridge : | |||
f) Make : Flowtec | |||
g) Cartridge MOC : Polypropylene | |||
h) Length: 20” | |||
i) Diameter : 4.0” | |||
j) Quantity: 4 no. | |||
k) Micron rating : 05 micron | |||
6 | HIGH PRESSURE PUMP | ||
Purpose | To feed the Reverse Osmosis Membrane at pressure more than the osmotic pressure taking into consideration flux rate, flow and recovery. | ||
Specifications | a) MOC : Stainless Steel | ||
b) Type : Vertical Multistage | |||
c) Flow Rate : 10500 liters per hour | |||
d) Head : 120 mwc | |||
e) Power Required : 5 HP | |||
f) Electrical : 440 V, three phase , 50 hz | |||
g) Cycle : 2900 rpm | |||
h) Make CRI or Lubi | |||
7 | RO MEMBRANE | ||
Purpose | To remove the major part of TDS upto 98% by Reverse Osmosis Membranes arranged and designed to give adequate flow and recovery. | ||
Specifications | a) Type : Spiral Wounded | ||
b) Diameter of Membrane : 8.0 inch | |||
c) Length of Membranes : 1 Mt. | |||
d) No. of Membranes : 5 | |||
e) Recovery per Membrane : 10-15% | |||
f) Salt Rejection per Membrane : 98-99% | |||
g) Make of Membranes : Toray or Equilent | |||
h) System Recovery : 45 -55 % | |||
8 | RO PRESSURE TUBE | ||
Purpose | To pack Reverse Osmosis Membranes and operate at high pressure up to 300 psi | ||
Specifications | a) MOC : FRP Composite | ||
b) Diameter of Pressure Vessel : 8.2 inch | |||
c) Length of Pressure Vessel : 120” | |||
d) No. Pressure Vessels : 2 | |||
e) No. of Membrane per Vessel : 2 and 3 | |||
f) Make : Seaflo, Shark or Equilent | |||
g) Position : Horizontal, Series | |||
h) Arrays : 2 No. | |||
9 | ELECTRICAL PANEL | ||
Purpose | A control panel is provided as a safety measure for the pumps & other electrical items. | ||
Specifications | a) Complete Starters, Overload relays, and single-phase preventor for Pump. | ||
b) Voltmeter, Ammeter, MCB’s, indicating lights | |||
c) Push Buttons | |||
10 | INSTRUMENTATION | ||
Purpose | a) Flow Meter : To measure the online flow of water | ||
b) Low Pressure Switch : To protect RO pump from dry running | |||
c) High Pressure Switch : To protect RO pump from back pressure | |||
d) Pressure Gauges : For calculate ^P for each unit in RO system | |||
Specifications | Rota Meter : | ||
Quantity : 2 Nos.( permeate & reject line) | |||
Range : 1.0 cu.m. per hour | |||
Make : Flowtec | |||
Pressure Switch : | |||
Quantity : 2 No.(Low & High) | |||
Range : 0-450 psi | |||
Make : Indfos, India | |||
Pressure Gauges : | |||
Quantity : 6 No. | |||
Range : 0 – 7 bar | |||
Dail Size : 6 inches | |||
Type : Bourdon | |||
Make : H-Guru | |||
11 | PLUMBING & FITTINGS | ||
a) Valves, pipelines RO module is in upvc, | |||
c) The System will be on common SS base frame | |||